Taco's Fast Fill boiler feed reducing valves are the perfect solution to low pressure problems in your hydronic system. The adjustable pressure range of the Fast Fill line makes it easy to optimize your system. Set your desired system pressure, and the 329-T3 will maintain that pressure by adding water to your system automatically. An internal check prevents your system from emptying in the event of a pressure failure. Purging a system with Fast Fill valves is a breeze as the Fast Fill lever may be locked in the open position, overriding typical circulation processes.
California residents see
Warning: This product can expose you to chemicals including Lead which is known to the State of California to cause Developmental Harm.
Warranty WarrantyA warranty is a safeguard from defects in manufacturing and can vary in length and terms. To see the manufacturer's warranty statement, click on the Manuals tab. Learn More
1 Year
Reviews
Taco 329-T3 Reviews & Ratings
Be the First to Write a Review
Do you own this product? Please share your insights with fellow shoppers.
Product Q&A
(1)
Product QuestionsAnswered by Bob, the Heating Product Expert
How do you lower pressure on this valve? Mine is delivering 30 PSI to the boiler and making relief valve drip.
Chris
from Colorado
December 02, 2016
Answer
The boiler feed valve should be factory set at 12 psi, but there are a couple things you can check to make sure it is set properly. First, make sure the fast fill lever is in the "A" position. If the pressure is still too high, loosen the lock nut on top and turn the screw counterclockwise several turns. Then release the pressure in your system and slowly turn the screw clockwise until your gauge reads the desired pressure. Finally, re-tighten the lock nut. For further details, see page 2 of the instruction manual.